2025-02-19 16:24:37.00000SHEET E1:
 1] INVERTER MAXIMUM AC OUTPUT CURRENT SHOWN IN SUMMARY
 TABLE IS INCORRECT (3.19A VS. 1.21A). THIS AFFECTS ALL
 SUBSEQUENT CALCULATIONS AND VALUES ON THIS SHEET AND ON
 MULTIPLE OTHER SHEETS; CORRECT ALL SHEETS TO CORRESPOND
 TO THE CORRECT INVERTER OUTPUT VALUES.
 2] REVISE THE CONDUIT SIZE BETWEEN THE COMBINER AND PV
 DISCONNECT AND BETWEEN THE PV DISCONNECT AND THE MSP;
 3/4" NOT APPROVED FOR INDICATED CONDUCTORS.
 ALTERNATIVELY, CHANGE CONDUCTOR SIZES TO #6 CU WITH #8
 CU EGC. (SEE ITEM #2 ON SHEET E3 NOTES).
 3] THE SUMMARY TABLE FOR THE MODULES SHOWS INCORRECT
 VALUES FOR THE PROPOSED 410W MODULE; CORRECT TO MATCH
 MANUFACTURER'S SPECIFICATIONS.
  
 SHEET E2: CORRECT PER ITEM #4 LISTED FOR SHEET E1
  
 SHEET E3:
 1] CORRECT PER ITEM #4 LISTED FOR SHEET E1
 2] THE #6 CONDUCTOR SIZE (UPPER LEFT HAND CORNER) IS
 INCONSISTENT WITH THE CONDUCTOR SIZE SHOWN ON SHEET E1.
 (SEE ITEM #2 ON SHEET E1 NOTES).
  
 SHEET E4: SHOW CORRECT COMBINED INVERTER OUTPUT OF
 47.19A ON ALL AC CURRENT LABELS.
  
 MULTIPLE SHEETS: THE "SCOPE OF WORK" TABLE AT THE
 BOTTOM OF THE SHEET SHOWS THE AC & DC OUTPUT VALUES
 REVERSED.
  
  