Plan Review Notes
Plan Review Notes For Permit 25011000
Permit Number 25011000
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-02-25 16:58:21.00000REFERENCE #: 25011000
  
 PROJECT: HIGHLANDS COUNTY EOC BUILDING ADDITION
  
 LOCATION: 6850 S GEORGE BLVD (7205)
  
 CONTRACTOR:
  
 OCCUPANCY:
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
  
 APPROVED WITH COMMENTS (SEE COMMENTS ON PLANS AND
 BELOW)
  
 NFPA 1 AND 101 - 2021 NOT 2018
 DOORS 109 AND 114 – SHALL BE 90 MIN DOORS
 ADD EMERGENCY LIGHTS IN BATHROOMS
 LABEL BREAKER FOR EMERGENCY LIGHTS/EXITS
  
 HIGHLY SUGGEST SPRINKLER SYSTEM FOR THE LOCATION DUE TO
 SLEEPING ROOMS DURING ACTIVATION.
  
  