Plan Review Notes
Plan Review Notes For Permit 25010804
Permit Number 25010804
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2025-03-07 07:57:31.00000PLAN REVIEW#: 25010804
 PROJECT: ARCHBOLD CHEMISTRY LAB REMODEL LOCATION: 123
 MAIN DR, VENUS, FL OCCUPANCY:
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 3/6/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
  
 DENIED
 COMMENT #1 - PLANS DO NOT SHOW FDC LOCATION FOR
 SPRINKLER SYSTEM, RISER LOCATION FOR SPRINKLER SYSTEM,
 OR FIRE LINE.
 RESPONSE: ONLY THE "CHEMICAL LABORATORY UNIT" REQUIRES
 FIRE SUPPRESSION PER NFPA 45. THE REMAINDER OF THE
 LABORATORY FALLS UNDER NFPA 1.1.3(1)(A), AS ALL
 QUANTITIES OF HAZARDOUS AND/OR FLAMMABLE LIQUIDS ARE
 RESTRICTED TO THE "CHEMICAL LABORATORY UNIT."
 A DRY CHEMICAL SUPPRESSION SYSTEM INSTALLED IN
 ACCORDANCE WITH NFPA 17 HAS BEEN SPECIFIED TO BE
 INSTALLED IN THE "CHEMICAL LABORATORY UNIT," AS NOTED
 PER NFPA 45
 6.1.2.2. THIS LABORATORY UNIT HAS BEEN SEPARATED FROM
 THE REMAINDER OF THE LABORATORY WITH A I-HOUR FIRE
 SEPARATION PER THE TABLE 5.1.1 IN NFPA 45.
 ADDED NOTE TO PAGE 4 FOR CLARITY.
 A.6.1.2 THE BASIC PHILOSOPHY OF NFPA 45 IS TO PROTECT
 LABORATORY WORK AREAS WITH SPRINKLERS IN ACCORDANCE
 WITH NFPA 13. IF A HAZARD ASSESSMENT SHOWS THAT THE
 PRESENCE OF WATER-REACTIVE MATERIALS WOULD CREATE A
 SERIOUS FIRE OR PERSONNEL HAZARD IN THE EVENT OF THE
 DISCHARGE OF SPRINKLER WATER, A NONWATER AUTOMATIC FIRE
 EXTINGUISHING SYSTEM DESIGNED TO PROTECT THE PORTION OF
 THE LAB WORK AREA CONTAINING WATER-REACTIVE MATERIALS
 IS ACCEPTABLE. NFPA 45-6.1.2.1 WHERE WATER WILL CREATE
 A SERIOUS FIRE OR PERSONNEL HAZARD, A SUITABLE NONWATER
 AUTOMATIC EXTINGUISHING SYSTEM SHALL BE PERMITTED TO BE
 AN ACCEPTABLE SUBSTITUTE FOR SPRINKLERS.
 THIS CODE IS USED IF THE WATER FROM THE SPRINKLER
 SYSTEM WOULD CREATE A SERIOUS FIRE OR PERSONNEL HAZARD.
 SEE IF THE ITEMS ARE WATER REACTIVE IN THE LAB?
 REVIEW FEE - $100 + INSPECTION FEE $50 = $150
  
2025-02-10 10:49:34.00000REVISED DRAWINGS WITH CORRECTIONS AND RESPONSES
 FORWARDED TO JASON RAPER