Plan Review Notes
Plan Review Notes For Permit 25010804
Permit Number 25010804
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-01-28 11:16:59.00000PLAN REVIEW #: 25010804
  
 PROJECT: ARCHBOLD CHEMISTRY LAB REMODEL
  
 LOCATION: 123 MAIN DR, VENUS, FL
  
 OCCUPANCY:
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 DATE: 1/28/25
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED –
  
 • PLANS DO NOT SHOW FDC LOCATION FOR SPRINKLER SYSTEM,
 RISER LOCATION FOR SPRINKLER SYSTEM, OR FIRE LINE.
 • PLANS INDICATE FIRE ALARM NOT REQUIRED. BUILDING HAS
 FIRE ALARM ALREADY – WILL REQUIRE TO UPDATE IN THIS
 AREA. PLUS, THE SPRINKLERS SYSTEM WILL BE REQUIRED TO
 BE HOOKED TO THE FIRE ALARM SYSTEM. (TAMPER AND FLOW
 ALARMS)
 • LIFE SAFETY PLANS – FIRE EXTINGUISHERS CHANGE SEE
 PLANS – ELECTRICAL PLANS SHOW EXIT INTO HALLWAY BUT NOT
 ON THE LIFE SAFETY PLAN PLUS THOSE DOORS SWING INTO THE
 LAB NOT THE HALL
 • ELECTRICAL PLANS – DO NOT SHOW THE EMERGENCY LIGHTS
 THAT MATCH THE LIFE SAFETY PLAN
  
 • WILL REQUIRE PLANS FOR THE SPRINKLER SYSTEM AND
 UPDATED FIRE ALARM PLANS
  
 REVIEW FEE – $100 + INSPECTION FEE $50 = $150
  
  
 ... PLEASE BE ADVISED THIS REVIEW OF PLANS SUBMITTED IS
 A CURSORY REVIEW TO ASSIST THE CONTRACTOR IN COMPLIANCE
 WITH APPLICABLE FIRE SAFETY CODES. THIS REVIEW IS NOT
 INTENDED TO BE A FINAL APPROVAL OF THE SUBMITTED PLANS.
 IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE
 THAT THE PLANS ARE IN COMPLETE COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES STATE STATUTES AND LOCAL
 ORDINANCE. IN THE EVENT THAT FURTHER EXAMINATION OR
 SITE INSPECTION REVEALS AREAS OF NON-COMPLIANCE. IT
 SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY, AT THEIR
 SOLE EXPENSE TO BRING THOSE AREAS IN COMPLIANCE. FIRE
 MARSHAL’S OFFICE ASSUMES NO RESPONSIBILITY FOR THE
 CONTRACTOR'S FAILURE TO BE IN COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES, STATE STATUTES AND LOCAL
 ORDINANCES.
  