2025-01-23 11:18:34.00000SHEET PV-4:
 1] CONDUCTORS SUPPLYING 150A BACKUP LOAD CENTER ARE
 UNDERSIZED
 2] 80A PV BREAKER IN EXISTING SERVICE PANEL, BASED ON
 GIVEN INFORMATION, DOES NOT COMPLY WITH 705.12 (B)(3)
 3] CONDUCTORS ON LINE AND LOAD SIDES OF TWO KNIFE-BLADE
 SAFETY SWITCHES MAY BE MIS-IDENTIFIED; THESE SWITCHES
 WILL NOT PROVIDE ADEQUATE GUTTER SPACE FOR THESE
 CONDUCTORS, AND MAY NOT INCORPORATE LUGS SUFFICIENT FOR
 250 KCMIL AWG. CORRECT CONDUCTOR SIZES AS NECESSARY.
  
 SHEET PV-7: THE VALUE SHOWN ON THE AC CURRENT LABEL IS
 INCORRECT.