Plan Review Notes
Plan Review Notes For Permit 25010748
Permit Number 25010748
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2025-02-04 09:28:52.00000SHEET PV-4:
 1] SHOW CORRECT SIZE OF EXISTING SYSTEM STRING INVERTER
 (OR MICROINVERTERS, IF PRESENT). "SOLAREDGE 440W" IS
 INACCURATE.
 2] THERE ARE TWO DIFFERENT CALLOUTS SHOWN ON THE
 CONDUCTORS BETWEEN THE NEW 3.8 KW STRING INVERTER AND
 THE 60A DISCONNECT. SHOW ONLY ONE CORRECT CONDUCTOR
 SIZE.
  