2025-01-22 16:27:53.00000SHEET PV-4:
 1] SHOW SIZE OF STRING INVERTER ON EXISTING SYSTEM
 2] THERE ARE TWO DIFFERENT CONDUCTOR IDENTIFICATION
 LABELS SHOWN ON THE CONDUCTORS BETWEEN THE NEW 3.8 KW
 INVERTER AND THE 60A DISCONNECT. SHOW ONLY ONE CORRECT
 CONDUCTOR SIZE.
 3] A BACKFED 100A PV BREAKER IS INDICATED IN THE
 EXISTING 200A-RATED MAIN SERVICE PANEL. THE COMBINED
 RATING OF ALL BREAKERS IN THIS PANEL (EXCEPT UTILITY
 MAIN) MUST NOT EXCEED THE RATING OF THE BUSBAR AND
 PROPER LABELING IS REQUIRED FOR THIS CONDITION PER
 705.12 (B)(3)(3).
 ALTERNATIVELY, USE A DIFFERENT METHOD OF
 INTERCONNECTION.