Plan Review Notes
Plan Review Notes For Permit 25010657
Permit Number 25010657
Review Stop BUILDING
Sequence Number 4
Notes
Date Text
2025-04-10 16:55:28.00000SHEET PV4: PROVIDE AN ARTICLE 220 FEEDER LOAD
 CALCULATION SHOWING THAT BACKED-UP LOADS SUPPLIED FROM
 THE TESLA GATEWAY DO NOT EXCEED 60 AMPS. THESE LOADS
 WILL BE CONNECTED TO THE 60A PROTECTED FEEDER FROM THE
 SERVICE PANEL;
 THIS FEEDER MUST BE CAPABLE OF SUPPLYING THESE LOADS
 WITHOUT THE CONSIDERATION OF SOLAR OR ESS AVAILABILITY.
2025-04-10 10:32:09.00000PERMITSARASOTA@FREEDOMFOREVER.COM CORRET PLANS