Plan Review Notes For Permit 25010657
Permit Number 25010657
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2025-03-25 13:42:29.00000SHEET PV-4:
 1] SHOW CONDUCTOR SIZE SUPPLYING BACKUP LOAD CENTER
 2] GIVEN THE CIRCUIT BREAKER RATINGS TO REMAIN IN THE
 MSP (PER THE PANEL SCHEDULE ON SHEET PV-5B), THE
 INSTALLATION DOES NOT COMPLY WITH 705.12 (B)(3)(3).
 THIS NEC SECTION SPECIFIES THE SUM OF BOTH LOAD AND
 SUPPLY DEVICES EXCLUDING THE MAIN BREAKER SUPPLYING THE
 PANELBOARD.