2025-03-13 09:47:34.00000REVIEW AND CORRECT PLANS FOR CONSISTENCY. THIS IS THE
 7TH REVIEW OF THIS SET OF PLANS. VERIFY ALL CORRECTIONS
 PRIOR TO SUBMISSION.
  
 SHEET PV-5 & PV-6, ASSUMING (29) IQ8-AC MICROINVERTERS
 @ 1.45A EACH, PER PROPOSED SCOPE OF WORK:
 1] INTERCONNECTION CALCULATION AT BOTTOM OF BOTH SHEETS
 SHOWS INCORRECT INVERTER DATA.
 2] INVERTER SPECIFICATION TABLE AT TOP OF BOTH SHEETS
 SHOWS INCORRECT INVERTER OUTPUT WATTAGE.
 3] CHANGE SYSTEM OVERCURRENT PROTECTION TO 60 AMPS (60A
 FUSES).
 4] SHEET PV-5 SHOWS 33 MODULES IN THE ONE-LINE DIAGRAM;
 CHANGE TO 29 MODULES PER PROPOSED SCOPE OF WORK.
  
 SHEET PV-7: CHANGE AC CURRENT OUTPUT LABEL TO SHOW
 42.05A. 29 X 1.45 = 42.05.
  
  
  