2025-03-06 13:49:08.000001] SHEET PV5: MODULE SPECIFICATION TABLE IN UPPER LEFT
 CORNER OF SHEET DOES NOT CORRESPOND TO SPECIFIED SYSTEM
 MODULES. SHOW VALUES FOR 450W MODULES AS SPECIFIED IN
 COVER SHEET.
 2] SHEET PV7: AC CURRENT LABEL SHOULD SHOW A VALUE OF
 32 AMPS. PER 690.54, THIS VALUE REPRESENTS ACTUAL
 MAXIMUM INVERTER OUTPUT WITHOUT THE APPLICATION OF
 DEMAND FACTORS. THE APPLICATION OF A 125% DEMAND FACTOR
 IS USED FOR SIZING EQUIPMENT, CONDUCTORS, AND
 OVERCURRENT PROTECTION.