Plan Review Notes For Permit 25010433
Permit Number 25010433
Review Stop BUILDING
Sequence Number 10
Notes
Date Text
2025-04-10 08:34:59.00000CONDITIONAL APPROVAL CONTINGENT ON THE FOLLOWING (NOTED
 ON PLANS):
 1] SHEET PV5, IDENTIFY STRING INVERTER BY MARKING THE
 APPROPRIATE LINE ON THE MANUFACTURER'S LABEL OR BY
 AFFIXING A PERMANENT LABEL TO THE INVERTER IN THE FIELD
 2] SHEET PV7, AFFIX MAXIMUM SYSTEM DC VOLTAGE LABEL TO
 INVERTER PER 690.53
2025-04-09 09:08:19.00000REVISED PERMTTING@SUNWAVEENERGY.BIX