Plan Review Notes
Plan Review Notes For Permit 25010433
Permit Number 25010433
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-01-15 15:26:06.00000PLANS CONTAIN MULTIPLE INCONSISTENCIES; REPLACE OR
 CORRECT AS BELOW.
 1] SHEET PV1 SCOPE OF WORK: OCPD SIZE DOES NOT
 CORRESPOND TO THAT SHOWN IN THE RISER DIAGRAMS ON
 SHEETS PV5 & PV6.
 2] SHEET PV1 SCOPE OF WORK: QUANTITY OF MODULES DOES
 NOT CORRESPOND TO QUANTITY INDICATED IN RISER DIAGRAM
 ON SHEETS PV5 & PV6.
 3] SHEETS PV5 & PV6: IN TOP LEFT CORNER OF SHEETS, THE
 VALUES SHOWN IN THE MODULE AND INVERTER SPECIFICATION
 TABLES DO NOT CORRESPOND TO THOSE SHOWN ON THE
 EQUIPMENT SPECIFICATION SHEETS.
 4] SHEET PV7: UPDATE AC CURRENT LABEL TO REFLECT TOTAL
 MAXIMUM OUTPUT CURRENT OF SYSTEM BASED ON PROPOSED
 MICROINVERTER QUANTITY AND MODEL.