Plan Review Notes
Plan Review Notes For Permit 25010375
Permit Number 25010375
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-01-10 14:05:18.000001] SHEET L1: PER 690.54, SHOW AN AC CURRENT/VOLTAGE
 LABEL TO BE AFFIXED TO THE GATEWAY INDICATING THE TOTAL
 COMBINED SYSTEM OUTPUT (BOTH INVERTERS COMBINED). THIS
 REQUIREMENT DOES NOT PROHIBIT AFFIXING SEPARATE AC
 CURRENT/VOLTAGE LABELS TO EACH INVERTER INDICATING THE
 OUTPUT OF EACH.
 2] SHEET D7: CHANGE THE IDENTIFIER ON THE GATEWAY IN
 THE DIAGRAM TO A "GATEWAY 3" TO AGREE WITH THE
 EQUIPMENT SCHEDULE ON SHEET E1.
2025-01-10 13:23:50.00000O.GONZALEZ@WINDMARHOME.COM