Plan Review Notes
Plan Review Notes For Permit 24120777
Permit Number 24120777
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-02-28 12:25:32.00000I HAVE A COUPLE OF COMMENTS.
 FIRST, A SPRINKLER PROFESSIONAL NEEDS TO BE INCLUDED TO
 MAKE SURE THE SPRINKLER SYSTEM IS ADJUSTED TO FIT THE
 PROPOSED BUILDING INTERIOR TO INCLUDE DESIGN AND
 FUNCTION. ALSO IF YOU CAN CONFIRM WITH ERIC BUT I THINK
 WE ( YOU THE COUNTY AND ME THE CITY) WOULD REQUIRE A
 PERMIT TO MAKE SURE THAT THIS PART GETS DONE. SO IF YOU
 CAN CHECK WITH ERIC DO WE REQUIRE A PERMIT FOR THIS
 SPRINKLER PROCESS FOR THIS PROJECT.
 SECOND I SEE NOTATIONS FOR FIRE EXTINGUISHERS BUT I DO
 NOT SEE ANY ACTUALLY NOTED ON THE PLAN. NOT A BIG DEAL
 AND WE CAN HOLD UP THE CO TO MAKE SURE THE
 EXTINGUISHERS ARE RIGHT, BUT WOULD BE CLEANER PROCESS
 IF IT WAS DONE NOW TO SHOW THEM. THEY WILL NEED A CLASS
 K DUE TO FRYERS AND THEN A STANDARD ONE, BUT 1 IN EACH
 PART (KITCHEN AND DINING AREA) WOULD BE IDEAL.
 THIRD, THEY REFERENCE A HOOD SYSTEM AND DEEP FRYERS,
 THEY WILL NEED A SEPARATE PERMIT FOR THIS TO TRACK THE
 HOOD SYSTEM.
 FOURTH, SIMPLE FIX BUT THEY SHOW AN EMERGENCY LIGHT
 OVER THE KITCHEN “EXIT” DOOR THIS NEEDS TO BE CHANGED
 TO “EXIT SIGN WITH EMERGENCY LIGHT WITH BATTERY BACKUP”
  
 OTHER THEN THOSE ITEMS I SEE NO ISSUES. LET ME KNOW IF
 YOU WANT ME TO LIKE STAMP THESE WITH THESE NOTES
 ATTACHED OR IF YOU WANT TO ADDRESS THESE ITEMS THEN THE
 APPROVAL PART?
  