-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24120604
Permit Number 24120604
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-12-18 14:24:08.00000SHEET PV-4: SUPPLY-SIDE CONDUCTORS MUST BE MINIMUM #6
 CU AND NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR,
 705.10 (B).
2024-12-18 08:57:32.00000PERMITSARASOTA@FREEDOMFOREVER.COM
  