Plan Review Notes For Permit 24120551
Permit Number 24120551
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2025-05-06 14:46:06.00000SHEET PV-2A: SHOW THE PHYSICAL LOCATION OF THE 100A
 FUSED "GENERATIONAL" DISCONNECT INDICATED ON SHEET
 PV-4. IF USED, THIS DISCONNECT MUST BE ON THE EXTERIOR
 OF THE HOUSE AND MUST BE EFFECTIVELY IDENTIFIED AS A
 PV/ESS DISCONNECTING MEANS.
 SHEET PV-7: POST THE CORRECT AMPERAGE VALUE ON THE AC
 CURRENT/VOLTAGE LABEL.