Plan Review Notes
Plan Review Notes For Permit 24120551
Permit Number 24120551
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-12-17 14:38:17.000001] CHANGE JOB SCOPE DESCRIPTION IN RIGHT HAND PAGE
 COLUMN TO REFLECT ALL PROPOSED WORK, I.E, LIST BOTH
 INVERTERS AND GATEWAY.
 2] CHANGE TOTAL AC OUTPUT IN RIGHT HAND PAGE COLUMN TO
 REFLECT COMBINED OUTPUT OF BOTH INVERTERS.
 3] COMPLETE AC CURRENT LABEL ON SHEET PV-7 TO REFLECT
 TOTAL PROPOSED PV SYSTEM OUTPUT.
 4] REWORK LOAD CALCULATIONS ON SHEET PV-5A. CALCS ON
 BOTH BACKUP PANEL AND ISOLATED LOAD PANEL INCLUDE SOME
 OF THE SAME LOADS; SMALL APPLIANCE AND LAUNDRY LOADS
 ARE MISSING; AS SHOWN, THE COMBINED DEMAND EXCEEDS THE
 200A SERVICE RATING.
  