Plan Review Notes For Permit 24120307
Permit Number 24120307
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-12-26 07:51:57.00000OR BK 3086 PG 1813 IN ONBASE
2024-12-10 16:10:14.00000SHEET PV4: 125% OF INVERTER OUTPUT PLUS RATING OF
 OVERCURRENT DEVICE PROTECTING THE BUSBAR EXCEEDS 120%
 OF THE BUSBAR RATING. (47.5 X 1.25) + 200 = 259A. 200 X
 1.2 = 240A.
 SEE 705.12 (B)(3)(2).