Plan Review Notes
Plan Review Notes For Permit 24110910
Permit Number 24110910
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-12-18 14:12:29.00000SHEET E-01:
 PROTECT THE EXISTING INTERIOR PANEL AND THE FEEDERS
 SUPPLYING IT AT NO MORE THAN 150A OR REPLACE FEEDER
 CONDUCTORS AND INTERIOR PANEL WITH 200A RATED (IN THIS
 CASE PROTECTED BY 200A ATS BRKR).
 EXISTING FEEDER CONDUCTORS AND INTERIOR PANEL ARE RATED
 FOR 150A AND ARE PROPOSED TO BE SUPPLIED BY BOTH
 UTILITY AND PV SOURCES WITH A COMBINED INPUT EXCEEDING
 150A.
 SEE 705.12 (B)(1) & (2)