Plan Review Notes For Permit 24110766
Permit Number 24110766
Review Stop BUILDING
Sequence Number 7
Notes
Date Text
2026-04-17 16:30:42.00000SUBMITTED AS AS-BUILT PLANS TO SATISFY INSPECTION
 DEFICIENCIES. THE FOLLOWING CORRECTIONS ARE REQUIRED:
 SHEET PV4: REMOVE NOTATION OF NEUTRAL-GROUND BOND IN
 GATEWAY; SHOW NEUTRAL-GROUND BOND IN MAIN SERVICE
 DISCONNECT.
 SHEET PV-4E: CORRECT CONDUCTOR TABLE TO MATCH ONE-LINE
 DRAWING, SHOWING CORRECT CONDUCTOR SIZES FOR EACH
 APPLICATION.