2025-03-14 16:00:24.00000THE FOLLOWING ITEMS HAVE NOT BEEN ADDRESSED FROM THE
 PREVIOUS REVIEW:
  
 1] SHEETS PV-4, PV-4A, PV-4B, PV-4C, PV-4D, & PV-4F:
 REMOVE EQUIPMENT GROUNDING CONDUCTOR FROM SUPPLY-SIDE
 TAP CONDUCTOR SET. THE SYSTEM WILL BE BONDED TO GROUND
 VIA THE GROUNDED CIRCUIT CONDUCTOR. REFERENCE 250.25
 (A).
  
 2] SHEET PV-4E: PROVIDE MANUFACTURER'S SPECIFICATION
 SHEET FOR 150A PV BREAKER, SHOWING COMPATIBILITY WITH
 EXISTING LOAD CENTER, OR, USE ALTERNATE INTERCONNECTION
 METHOD.
  
 3] BUILDINGS E & G: A MINIMUM 48 INCH-WIDE FIREFIGHTER
 ACCESS PATH MUST EXTEND AROUND THE ENTIRE PERIMETER OF
 THE ROOF (ALL FOUR SIDES). REFERENCE FFPC 11.12.2 FOR
 BUILDINGS OTHER THAN DWELLING UNITS; NO EXCEPTION
 ALLOWED BY HC FIRE MARSHALL.
  
 4] NOTE THAT AN ELECTRICAL PERMIT WILL BE REQUIRED
 (BEFORE THIS PERMIT IS ISSUED) TO COVER ANY SCOPE OF
 WORK THAT INVOLVES MODIFICATION OF THE SERVICE, I.E.,
 THE INSTALLATION OF A GATEWAY AS A NEW SERVICE
 DISCONNECT.
  
2025-03-14 10:06:42.00000RCEVD REVISED SOLAR PLAN, SUPPOSEDLY CORRECT ONE.