Plan Review Notes
Plan Review Notes For Permit 24110766
Permit Number 24110766
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-11-25 15:17:35.000001] PV PLANS MUST BE SIGNED AND SEALED BY A FLORIDA
 LICENSED PROFESSIONAL ENGINEER.
 2] THE APPLICANT IS A CVC SOLAR CONTRACTOR. BUILDING F
 INCLUDES MODIFICATIONS TO THE ELECTRICAL SYSTEM; AS
 SUCH, A LICENSED ELECTRICAL CONTRACTOR IS REQUIRED TO
 OBTAIN A PERMIT FOR AT LEAST THIS PORTION OF THE
 PROJECT.
 3] SHEET PV4-E (BUILDING F ONE-LINE DIAGRAM) INDICATES
 A BACKFED PV BREAKER INSTALLED IN A 200A-RATED EXISTING
 MAIN SERVICE PANEL. SHOW ALL OTHER CIRCUIT BREAKERS
 INSTALLED OR TO BE INSTALLED IN THIS PANEL TO VERIFY
 COMPLIANCE WITH 705.12 (B)(3)(3).
 4] BUILDINGS G AND E MUST SHOW A MINIMUM 48" WIDE
 PERIMETER FIRE ACCESS PATH PER THE 8TH EDITION FLORIDA
 FIRE PREVENTION CODE 11.12.3.3.2.1. THIS REQUIREMENT
 WILL BE WAIVED IF THE BUILDINGS ARE NON-HABITABLE
 STRUCTURES.
 5] VALUATION CLAIMED ON THE PERMIT APPLICATION DOES NOT
 APPEAR TO BE CORRECT BASED ON THE SCOPE OF WORK, AND
 WOULD NOT COVER EVEN THE TYPICAL COST OF THE MODULES.
 SHOW CORRECT JOB VALUATION ON PERMIT APPLICATION.