-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24110708
Permit Number 24110708
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-12-31 10:52:02.00000SHEET PV-4: CHANGE EQUIPMENT GROUNDING CONDUCTOR TO
 MINIMUM #6 CU BETWEEN SERVICE AND BACKUP INTERFACE, AND
 BETWEEN BACKUP INTERFACE AND NEW BACKUP LOAD CENTER.
2024-12-30 15:01:29.00000PERMITSARASOTA@FREEDOMFOREVER.COM