-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24110134
Permit Number 24110134
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-11-05 15:54:04.00000SHEET PV-4: CONDUCTORS ON LINE SIDE OF PV DISCONNECT
 MUST BE MINIMUM #6 CU, 705.11 (B).