Plan Review Notes For Permit 24110071
Permit Number 24110071
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2025-01-02 16:17:01.00000PLAN REVIEW #: 24110071
  
 PROJECT: CRAVE
  
 LOCATION: 1249 US 27
  
 OCCUPANCY: WAREHOUSE
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 DATE: 12/23/24
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 REVIEW FEE – $1875 + INSPECTION FEE $50 = $1925
  
 APPROVED – WITH THE COMMENTS CORRECTED
  
 I HAVE MADE COMMENTS ON PLANS.
  
 FIRE EXTINGUISHERS IN RISER ROOM AND ELECTRICAL ROOM
 NEED TO MOVE NEXT TO THE EXIT DOOR. IN THE ASSEMBLY
 AREA FIRE EXTINGUISHER MOVED TO EXIT DOOR. ADD FIRE
 EXTINGUISHER IN LOBBY HALLWAY AT EXIT DOOR. WILL NEED
 TO ADD MORE FIRE EXTINGUISHERS IN WAREHOUSE DUE TO
 DISTANCE OF TRAVEL TO FIRE EXTINGUISHERS. (SEE PLANS)
 EVER EXIT SHOULD HAVE A FIRE EXTINGUISHER.
  
 IN THE WAREHOUSE AREA IF RACKING BLOCKS CLEAR VIEW OF
 EXIT SIGNS ADDITIONAL DIRECTIONAL EXIT SIGNS WILL BE
 NEEDED.
  
 FIRE ALARM AND SPRINKLER PLANS WILL BE REQUIRED BY
 CONTRACTOR THAT ARE COMPLETING THESE INSTALLATIONS.
  
 ... PLEASE BE ADVISED THIS REVIEW OF PLANS SUBMITTED IS
 A CURSORY REVIEW TO ASSIST THE CONTRACTOR IN COMPLIANCE
 WITH APPLICABLE FIRE SAFETY CODES. THIS REVIEW IS NOT
 INTENDED TO BE A FINAL APPROVAL OF THE SUBMITTED PLANS.
 IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE
 THAT THE PLANS ARE IN COMPLETE COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES STATE STATUTES AND LOCAL
 ORDINANCE. IN THE EVENT THAT FURTHER EXAMINATION OR
 SITE INSPECTION REVEALS AREAS OF NON-COMPLIANCE. IT
 SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY, AT THEIR
 SOLE EXPENSE TO BRING THOSE AREAS IN COMPLIANCE. FIRE
 MARSHAL’S OFFICE ASSUMES NO RESPONSIBILITY FOR THE
 CONTRACTOR'S FAILURE TO BE IN COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES, STATE STATUTES AND LOCAL
 ORDINANCES.
  