Plan Review Notes For Permit 24110071
Permit Number 24110071
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2024-12-20 08:44:59.00000PLAN REVIEW #: 24110071
  
 PROJECT: CRAVE
  
 LOCATION: 1249 US 27
  
 OCCUPANCY: WAREHOUSE
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 DATE: 12/19/24
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 REVIEW FEE – $1875 + INSPECTION FEE $50 = $1925
  
 THIS WAS ONLY QUICK REVIEW OF PLANS. HARD COPY NEEDED
 FOR FULL REVIEW.
 I WOULD PREFER TO HAVE HARD COPY OF THE PLANS TO SCALE.
 THIS IS SO I CAN WRITE COMMENTS ON PLANS AND RELOCATE
 FIRE EXTINGUISHERS AS NEEDED.
  
 JUST ON THE QUICK LOOK OF THE PLANS FIRE EXTINGUISHERS
 IN RISER ROOM AND ELECTRICAL ROOM NEED TO MOVE NEXT TO
 THE DOOR NOT THE BACK WALL. IN THE ASSEMBLY AREA FIRE
 EXTINGUISHER MOVED TO EXIT DOOR. CLASSROOM FIRE
 EXTINGUISHER MOVED TO EXIT DOOR. ADD FIRE EXTINGUISHER
 IN LOBBY HALLWAY AT EXIT DOOR.
  
 IN THE WAREHOUSE AREA IF RACKING BLOCKS CLEAR VIEW OF
 EXIT SIGNS DIRECTIONAL EXIT SIGNS WILL BE NEEDED.
  
 FIRE ALARM AND SPRINKLER PLANS WILL BE REQUIRED BY
 CONTRACTOR THAT ARE COMPLETING THESE INSTALLATIONS.
  
  