Date Text
2024-11-13 08:38:46.00000SHEET PV4: NO CHANGE TO INITIAL PLANS. NOTE INDICATES
 THAT THE 7.6 KW STRING INVERTER OUTPUT WILL BE
 PCS-CONTROLLED WITH A CURRENT OUTPUT SETTING OF 120A.
 SHOW PCS BUS OR SERVICE CONDUCTOR MONITORING
 SYSTEM/COMPONENTS THIS PLAN SHEET. SHOW PERMANENT LABEL
 INDICATING THE OUTPUT PARAMETERS OF THE PCS.
2024-11-12 09:52:40.00000PERMITSARASOTA@FREEDOMFOREVER.COM