Date Text
2024-10-28 16:05:47.00000SHEET PV-4: 125% OF INVERTER OUTPUT PLUS MAIN BREAKER
 RATING EXCEEDS 120% OF THE BUSBAR. (32 X 1.25) + 150 >
 150 X 1.20
 SEE NEC 705.12 (B)(3)(2).