Permit Number 24100306
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2024-11-18 08:37:43.00000SHEET PV-4: CONDUCTORS FROM SUPPLY-SIDE TAP TO PV
 DISCONNECT MUST BE MINIMUM #6 CU, 705.11 (B).
2024-11-15 14:38:18.00000REVISION PERMITSSARASOTA@FREEDOMFOREVER.COM