Plan Review Notes For Permit 24100091
Permit Number 24100091
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-10-02 16:36:36.00000SHEET PV4:
 1] SHOW CONDUCTOR SIZE BETWEEN COMBINER PANEL AND PV
 DISCONNECT
 2] CLEARLY INDICATE METHOD OF INTERCONNECTION. A 70A
 BACKFED BREAKER IS INDICATED; HOWEVER, A LINE SIDE TAP
 IS DRAWN. THE BACKFED BREAKER OPTION WILL NOT BE
 APPROVED DUE TO TOTAL SYSTEM OUTPUT AND EXISTING PANEL
 RATING.
 3] REMOVE BACKFEED FUSE SIZING TABLE FROM TOP LEFT
 CORNER OF SHEET.
  
 SHEET PV7: SHOW CORRECT CURRENT VALUE IN AC LABEL
  