-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24090658
Permit Number 24090658
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-09-24 14:37:46.00000SHEET PV4: CONDUCTORS BETWEEN SUPPLY-SIDE TAP AND PV
 DISCONNECT MUST BE MINIMUM #6 CU, 705.11 (B).
2024-09-20 15:46:57.00000PERMITSARASOTA@FREEDOMFOREVER.COM