-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24090538
Permit Number 24090538
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-09-18 14:48:09.00000PLANS MUST BE COMPLIANT WITH 8TH EDITION FLORIDA
 BUILDING CODE AND 2020 NATIONAL ELECTRICAL CODE.
 COMPLIANCE CERTIFICATION MUST APPEAR ON SHEET T-1
 (CURRENTLY SHOWS COMPLIANCE WITH A PREVIOUS CODE
 EDITION).
 ALTERNATIVELY, WILL ACCEPT ENGINEER'S LETTER
 REFERENCING PLANS AND ATTESTING TO COMPLIANCE AS
 REQUIRED.
  
 SHEET E-5: CHANGE UNGROUNDED CONDUCTORS BETWEEN 175A
 GENERATOR BREAKER AND ATS TO MINIMUM 2/0 CU.
2024-09-18 10:38:53.00000SHERYL.DENAN@SMARTLINKGROUP.COM