Plan Review Notes
Plan Review Notes For Permit 24090065
Permit Number 24090065
Review Stop BUILDING
Sequence Number 5
Notes
Date Text
2025-03-06 15:04:42.00000SHEET PV-6: RELOCATE PV FEEDER TAP INTERCONNECTION TO
 LOAD SIDE OF NEW 100A HOUSE DISCONNECT. THE CONCERN IS
 OVERLOADING THE BUS OF THE 150A METER-MAIN (IF ANY
 BRANCH OR FEEDER BREAKERS ARE INSTALLED) WHEN SUPPLIED
 BY BOTH UTILITY AND PV INPUTS [150 + (30.25 X 1.25)] >
 150 X 1.20.
 SEE 705.12 (B).
2025-03-06 07:45:54.00000REVISION MELAINA@LUNEXPOWER.COM