2024-08-26 09:10:32.00000NOC IN ON BASE. OR BK 3063 PG 1914
  
2024-08-20 14:29:35.00000SHEET PV4 (ONE-LINE): CONDUCTORS BETWEEN SUPPLY-SIDE
 TAP AND PV DISCONNECT MUST BE MINIMUM #6 CU; CONDUCTORS
 BETWEEN PV DISCONNECT AND SOLAR LOAD CENTER DO NOT HAVE
 SUFFICIENT AMPACITY FOR THE PROPOSED 60A OCPD. CHANGE
 CONDUCTOR SIZES AND/OR FUSES TO COMPLY WITH 705.11 (B)
 AND TBL. 310.16.
 RIGHT SIDEBAR (AND POSSIBLY AFFECTING DATA ON OTHER
 SHEETS): EXISING PV SYSTEM IS SHOWN INCORPORATING A
 .026 KW INVERTER. PLEASE VERIFY THE EXISTING EQUIPMENT.
2024-08-19 10:23:56.00000PERMITS SARASOTA