Plan Review Notes
Plan Review Notes For Permit 24070245
Permit Number 24070245
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-07-09 15:10:36.00000SHEET PV 4 INDICATES THE USE OF TWO POLES OF A QUAD
 BREAKER TO INTERCONNECT AN EXISTING PV SYSTEM, ALONG
 WITH A NEW BACKFED BREAKER TO INTERCONNECT THE PROPOSED
 SYSTEM.
 THE RELATIVE LOCATION OF THESE TWO CIRCUIT BREAKERS IS
 UNCLEAR; PLEASE PROVIDE ONE OF THE FOLLOWING TWO
 SOLUTIONS:
 1] INCLUDE PLAN LANGUAGE INDICATING THAT BOTH CIRCUIT
 BREAKERS WILL BE LOCATED ON THE OPPOSITE END OF THE BUS
 FROM THE MAIN (HORIZONTALLY SIDE-BY-SIDE), OR
 2] REDESIGN DRAWING TO COMBINE BOTH THE EXISTING AND
 PROPOSED PV SYSTEMS PRIOR TO ENTERING THE SERVICE
 PANEL. THIS METHOD WILL SHOW A SINGLE POINT OF
 INTERCONNECTION.