Date Text
2024-08-28 15:33:21.00000RE-WORK SHEET PV4. TEXT IS OVERLAPPING IN AT LEAST FOUR
 LOCATIONS, OVERCURRENT PROTECTION DOES NOT CORRESPOND
 WITH CONDUCTOR SIZES IN ALL LOCATIONS. ALL TEXT AND
 DIAGRAMS ON SHEET MUST BE CLEAR, ACCURATE, AND LEGIBLE,
 AND MUST INCLUDE THE FOLLOWING:
 1] SHOW ALL CONDUCTOR SIZES AND OVERCURRENT RATINGS
 2] SHOW EXISTING SYSTEM MICROINVERTER TYPE AND RATING
 3] SHOW QUANTITY OF EXISTING MODULES CONNECTED VIA
 LINE-SIDE TAP AND QUANTITY OF EXISTING MODULES COMBINED
 WITH NEW PROPOSED SYSTEM