-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24060052
Permit Number 24060052
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-08-06 12:11:10.00000SHEET E2 (ONE-LINE DIAGRAM): IQ8+ - 72-2-US
 MICROINVERTERS ARE SPECIFIED IN DIAGRAM; IQ8-60-2-US
 MICROINVERTERS ARE SPECIFIED IN SUMMARY CHART.
 CORRECT AS NECESSARY FOR CONSISTENCY. UNABLE TO
 DETERMINE CORRECT OCPD OR CONDUCTOR SIZE WITHOUT
 ACCURATE DATA.
2024-08-06 08:08:15.00000DAVID SCHILDTKNECHT
 
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved