Plan Review Notes For Permit 24050924
Permit Number 24050924
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-07-22 15:57:48.00000JOHN AND I IDENTIFIED THE FOLLOWING POSSIBLE ELECTRICAL
 ISSUES WITH THE PLANS YOU SENT, ALL ON SHEET E401-B:
  
 1] CHANGE CIRCUIT BREAKER SUPPLYING RTU-1 TO A 300 AMP
 TO COMPLY WITH MAXIMUM OVERCURRENT RATING LISTED ON
 SHEET H001 FOR THIS UNIT.
  
 2] REVISIT FEEDER SCHEDULE: CIRCUIT IDENTIFIER “E”
 APPEARS TWICE IN THE LIST AND IS NOT SHOWN IN ANY
 CALLOUT ON THE SHEET.
  
 3] IN THE RISER DIAGRAM, PANEL “R1” APPEARS TWICE;
 FEEDER CALLOUT “F” (#12 AWG) IS INCORRECT FOR THESE
 CONDUCTOR SIZES PROTECTED BY A 250A OCPD.
  
 4] INSERT NOTE FOR CONTRACTOR TO VERIFY HORSEPOWER
 RATING OF NEW BALER: 150A CIRCUIT BREAKER SUPPLYING #2
 AWG CONDUCTORS MUST COMPLY WITH 430.22 FOR MOTOR
 CIRCUIT CONDUCTORS AND WITH TBL. 430.52 FOR MOTOR
 GROUND-FAULT SHORT-CIRCUIT PROTECTION.
  
  