-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24050832
Permit Number 24050832
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-07-17 14:49:32.00000SHEETS PV4 & PV6: INDICATE UNDERGROUND CONDUCTORS ON
 SITE PLAN AND ON CONDUCTOR SCHEDULE; INSERT NOTE
 INDICATING MINIMUM UNDERGROUND CONDUIT COVER IN
 COMPLIANCE WITH TABLE 300.5. IF UNDERGROUND CONDUCTORS
 ARE SUPPLY-SIDE TAPS (AS SHOWN ON SHEET PV4), SHOW A
 WARNING RIBBON IN THE TRENCH IN COMPLIANCE WITH 300.5
 (D)(3).
2024-07-16 13:40:04.00000REVISED PLANS MELANIA@LUNEXPOWER.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved