2024-05-28 11:02:19.00000SHEET PV4 SHOWS PV DISCONNECT MOUNTED ON SIDE OF HOUSE
 ADJACENT TO INTERIOR HOUSE LOAD CENTER (PRESUMED
 INTENTION OF USING A FEEDER TAP FOR INTERCONNECTION)
 SHEET PV6 SHOWS A SUPPLY-SIDE TAP AT THE METER-MAIN
 WITH A BONDED NEUTRAL IN THE PV DISCONNECT.
 CLARIFY DRAWING TO SHOW CONSISTENCY OF INTERCONNECTION
 METHOD.
  