Date Text
2024-06-28 13:12:19.00000SHEET PV6:
 1] SHOW INTERCONNECTION AS "FEEDER TAP", NOT "SUPPLY
 SIDE CONNECTION"
 2] ADD #6 CU EQUIPMENT GROUNDING CONDUCTOR TO FEEDER
 TAP BETWEEN PV DISCONNECT AND ATS (CONDUCTOR ID #4).