Plan Review Notes For Permit 24050456
Permit Number 24050456
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-07-12 13:12:00.000001] PROVIDE STATEMENT OF REVISED VALUATION (AMENDED
 APPLICATION OR LETTERHEAD)
 2] SHEET PV4: UTILITY SERVICE TO DWELLING UNIT IS
 REDUCED TO A 100 AMP RATING BY THE CIRCUIT BREAKER IN
 THE PROPOSED TESLA GATEWAY. PROVIDE ACCURATE LOAD
 CALCULATION FOR THIS ELECTRICAL SERVICE TO SUBSTANTIATE
 THIS REDUCTION.
 3] SHEETS PV4 & PV7: FOR COMPLIANCE WITH 706.15, SHOW
 PERMANENT DURABLE LABELING INDICATING THE LOCATION OF
 THE BATTERY DISCONNECTING MEANS (BOTH AT THE GATEWAY
 AND ON THE POWERWALL) OR PROVIDE A SEPARATE SAFETY
 SWITCH OR STOP BUTTON WHICH WILL DISABLE BACKUP POWER.
 IN ALL CASES, THIS DISCONNECTING MEANS MUST BE ON THE
 EXTERIOR OF THE HOUSE AND BE EFFECTIVELY IDENTIFIED.