Plan Review Notes
Plan Review Notes For Permit 24050361
Permit Number 24050361
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-05-13 12:51:02.00000RECIEVED REVISION VIA WALK-IN
  
2024-05-10 15:49:29.00000SHEET PV-2 & PV-3: PROVIDE A READILY ACCESSIBLE RAPID
 SHUTDOWN INITIATION DEVICE ON THE EXTERIOR OF THE
 STRUCTURE PER 690.12 (C) (1). RAPID SHUTDOWN SHALL
 OCCUR BY THE OPERATION OF A SINGLE DEVICE, SUCH AS A PV
 DISCONNECT. THE USE OF MULTIPLE CIRCUIT BREAKERS IN A
 COMBINER PANEL IS NOT APPROVED FOR RAPID SHUTDOWN
 INITIATION.