Date Text
2024-04-10 14:46:18.00000SHEET PV-4: CONDUCTORS BETWEEN COMBINER PANEL AND PV
 DISCONNECT MUST BE MINIMUM #6 CU FOR INDICATED 60A
 OCPD.