2025-05-06 10:29:30.00000PLAN REVIEW #: 24040187
 PROJECT: SMOKE SHACK – BUILDING
 LOCATION: 123 US 27 N, LAKE PLACID
 OCCUPANCY: ASSEMBLY
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/6/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED WITH COMMENTS
 ITEMS ADDED ON PLANS:
  TRAVEL, DEAD END, COMMON PATH DISTANCES NEED
 ON PLANS ADDED TO THE PLANS.
  ELECTRICAL PANELS WILL REQUIRE BREAKERS TO BE
 LABELED FOR EXIT/EMERGENCY LIGHTS.
 SHALL SUBMIT SEPARATE PLANS FOR THE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM, KITCHEN HOOD SYSTEM,
 HOOD EXTINGUISHER SYSTEM, AND ALARM SYSTEM.
 REVIEW FEE – $400 + INSPECTION FEE - $50 = $450