Plan Review Notes For Permit 24040187
Permit Number 24040187
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-05-22 10:13:02.00000PLANS ARE INCOMPLETE. THE FOLLOWING ADDITIONS WILL NEED
 TO BE MADE AND PLANS RESUBMITTED FOR
 REVIEW.
 1. THERE ARE NO MECHANICAL PAGES. MECHANICAL PAGES WILL
 NEED TO BE ADDED.
 2. THE PLUMBING PLAN IS INCOMPLETE. PLUMBING PAGES MUST
 INCLUDE DRAINAGE DETAILS,
 SUPPLY DETAILS, GREASE TRAP DETAILS, ADA DETAILS, FLOOR
 DRAIN DETAILS, CHECK VALVES FOR ICE
 MACHINE AND BEVERAGE DISPENSER, WATER HEATER DETAILS,
 GAS LINES, CO2 LINES, FILTERS??ETC.
 3. THE ELECTRICAL PAGES ARE INCOMPLETE. THIS PROJECT
 WILL REQUIRE A LOAD CALCULATION. PLANS
 NEED TO INCLUDE A PANEL SCHEDULE AND RISER DIAGRAM.
 4. PLANS NEED TO INCLUDE NOTES TO INCLUDE (BUT NOT
 LIMITED TO) USE AND OCCUPANCY
 CLASSIFICATION, CONSTRUCTION TYPE, OCCUPANCY LOAD, FIRE
 CODE REFERENCE, ADDRESS SIZE AND
 LOCATION, KNOX BOX??(CHECK WITH FIRE MARSHAL), ETC.
 5. LIFE SAFETY PAGE IS INCOMPLETE, SEE FIRE MARSHAL
 NOTES.
 SINCERELY,
 ERIC R.