Plan Review Notes For Permit 24030618
Permit Number 24030618
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2024-04-09 08:49:42.00000TO USE BACKFED BREAKER IN COMBINER PANEL AS PV
 DISCONNECT/RAPID SHUTDOWN INITIATION, THE FOLLOWING
 ITEMS MUST BE INDICATED ON THE PLANS (SHEET E-601):
  
 1] INSTALL LISTED HOLD-DOWN DEVICE FOR BACKFED BREAKER,
 IN COMPLIANCE WITH 408.36 (D). FOR PLAN APPROVAL,
 INCLUDE MANUFACTURER'S SPECIFICATION SHEET ON THIS
 PRODUCT, SHOWING COMPATIBILITY WITH SELECTED LOAD
 CENTER.
 2] AFFIX LABEL INSIDE COMBINER PANEL (IMMEDIATELY
 ADJACENT TO BACKFED BREAKER) INDICATING PURPOSE AS PV
 DISCONNECT/RAPID SHUTDOWN SWITCH. FOR PLAN APPROVAL,
 SHOW SAMPLE OF THIS LABEL ON SHEET E-602.
 3] AFFIX LABEL ON EXTERIOR COVER OF COMBINER PANEL
 INDICATING THE PRESENCE OF A PV DISCONNECT/RAPID
 SHUTDOWN SWITCH WITHIN THE ENCLOSURE. FOR PLAN
 APPROVAL, SHOW SAMPLE OF THIS LABEL ON SHEET E-602.
  
2024-04-05 14:58:11.00000REVISED PLANS KELCIE@CASTAWAYSENERGY.COM