Plan Review Notes For Permit 24030618
Permit Number 24030618
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-03-21 12:51:26.00000SHEET E-601: SHOW A SEPARATE DISCONNECTING MEANS FOR
 THE PV SYSTEM COMPLYING WITH 690.13 (A), (B), (D), &
 (E). THE DISCONNECTING MEANS MUST BE READILY ACCESSIBLE
 AND LOCKABLE, AND IF INTENDED TO FUNCTION AS THE RAPID
 SHUTDOWN SWITCH, MUST BE LOCATED ON THE EXTERIOR OF THE
 HOUSE, 690.12 (C).
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET E-601.
  
 NOTE ADDED 4/4/24: TO CLARIFY INTENT OF ABOVE
 REQUIREMENT, SEE TEXT OF 690.12 (C), SECOND PARAGRAPH:
 "FOR A SINGLE PV SYSTEM, THE RAPID SHUTDOWN INITIATION
 DEVICE SHALL OCCUR BY THE OPERATION OF ANY SINGLE
 INITIATION DEVICE". NOTE REQUIREMENT IN PREVIOUS
 PARAGRAPH THAT THIS DEVICE MUST BE AT A READILY
 ACCESSIBLE LOCATION ON THE EXTERIOR OF ONE-FAMILY
 DWELLINGS. THIS INFORMATION HAS BEEN COMMUNICATED TO
 THE CONTRACTOR OF RECORD BY EMAIL. ALL ASSOCIATED
 EMAILS WILL BE RETAINED IN THE PERMIT FOLDER IN PDF
 FORMAT.
2024-03-20 09:18:19.00000EMAILED IN FROM KELCIE@CASTAWAYSENERGY.COM