-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24030368
Permit Number 24030368
Review Stop BUILDING
Sequence Number 4
Notes
Date Text
2024-05-28 10:41:04.00000SHEET PV 3.2: AC CURRENT/VOLTAGE LABEL MUST SHOW ACTUAL
 MAXIMUM COMBINED INVERTER OUTPUT OF 81.07A WITHOUT THE
 APPLICATION OF CONTINUOUS DEMAND FACTORS.
2024-05-24 15:47:34.00000LISA.KNOTE@MOMENTUMSOLAR.COM +
 FLPERMITS@MOMENTUMSOLAR.COM
  
 PREVIOUS REVISION REQUEST WAS APPROVED FOR UPDATES TO
 PAGE PV-3.2.
  
 ON 5/23/24, LISA ADVISED THAT IN ADDITION TO THE
 CORRECTIONS THAT WERE REQUIRED FOR PAGE PV-3.2,
 ADDITIONAL CHANGES WERE MADE TO THE PLANS, BUT THOSE
 CHANGES WEREN'T COMMUNICATED CLEARLY WHEN CORRECTIONS
 WERE SUBMITTED,
 WHICH RESULTED IN ONLY THE REQUESTED PAGE BEING
 FORWARDED FOR APPROVAL. NOW, THE ADDITIONAL CHANGES
 NEED TO BE REVIEWED...
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved